Seller Notes : “USED BUT TESTED AND EVERYTHING WORKING WELL !”
Features:Programmable
MPN :GCP-2245B/LSB
Controller Platform : OPERATOR INTERFACE PANEL
Key Features & Specifications
1. Core Control Functions
-
Speed Governing:
-
Isochronous/Droop Operation (±0.25% accuracy)
-
Engine RPM Range: 0–4,000 RPM (configurable)
-
-
Voltage Regulation:
-
±0.5% steady-state voltage control
-
Compatible with 1-phase (120/240V) & 3-phase (up to 600V) systems
-
-
Load Management:
-
kW/kVAR load sharing (for parallel gensets)
-
Load ramp rates: 1–100 kW/sec (adjustable)
-
2. I/O Configuration
-
Analog Inputs (6x):
-
4 × 4–20mA / 0–10V (temp, pressure, etc.)
-
2 × PT100/RTD (engine temp monitoring)
-
-
Digital Inputs (8x):
-
24V DC wet inputs (breaker status, start signals)
-
4 × configurable as pulse inputs (for fuel flow, etc.)
-
-
Outputs:
-
4 × Relay (5A @ 30V DC / 2A @ 250V AC)
-
1 × 4–20mA actuator output (governor control)
-
3. Communication Interfaces
-
Standard:
-
RS-485 Modbus RTU (terminals 45–46)
-
CANbus J1939 (engine data – terminals 47–50)
-
-
Optional (via expansion):
-
Ethernet (requires 8440-1150 module)
-
PROFIBUS DP (8440-1160 module)
-
4. Protection Features
-
Engine Safeties:
-
Overspeed (2-stage: Warning @ 110% + Shutdown @ 115%)
-
Low oil pressure (adjustable delay)
-
High coolant temp
-
-
Electrical Protections:
-
Over/under voltage (27/59)
-
Over/under frequency (81O/81U)
-
Reverse power (32)
-
5. Environmental Specifications
-
Operating Temp: -40°C to +85°C (-40°F to +185°F)
-
Humidity: 5–95% non-condensing
-
Vibration: 5G (5–500Hz, all axes)
-
Certifications: UL 508, CE, DNV-GL
6. Power Supply
-
Input Range: 9–36V DC (24V nominal)
-
Power Consumption: 12W typical / 18W max
-
Protections:
-
Reverse polarity (up to 60V)
-
Transient suppression (IEC 61000-4-5)
-
Model Breakdown (8440-1012 Rev B)
-
GCP-20: Base model (20 I/O points)
-
Rev B: Hardware revision (enhanced EMC shielding)
-
Firmware: v4.2.x (upgradable via Toolkit)
Configuration & Calibration
-
Software: Woodward Toolkit (v5.10+ recommended)
-
Auto-Tuning:
-
Governor PID self-tuning
-
AVR (Auto Voltage Regulator) calibration
-
-
Custom Logic:
-
16 function blocks for custom control strategies
-
8 timers/counters
-
Wiring Example (Speed Sensing)
MPU Connection: Terminal 33 (MPU+) → Magnetic Pickup Wire A Terminal 34 (MPU-) → Magnetic Pickup Wire B Shield → Ground terminal (ensure single-point grounding)
Typical Applications
-
Prime Power: 50–3000kVA diesel/gas gensets
-
Marine: ISO 8528-5 compliant installations
-
CHP Plants: Combined heat & power systems
-
Mission Critical: Data centers, hospitals