Condition:Used
Key Specifications
-
Model Identification
-
Part Number: 8440-1855
-
Revision: G (hardware/software version)
-
Series: EasyGen-2200 (5/P1 variant)
-
Type: Digital paralleling controller with integrated protection
-
-
Core Functions
-
Advanced Paralleling:
-
Isochronous/Droop load sharing (≤1% imbalance)
-
Closed transition transfer
-
32-unit maximum bus configuration
-
-
Protection Suite:
-
27/59 (under/over voltage)
-
81O/81U (over/under frequency)
-
Reverse power (32R)
-
Customizable alarm thresholds
-
-
-
Technical Parameters
-
Voltage Inputs: 50-600V AC L-L (configurable PT ratios)
-
Current Inputs: 1A or 5A CTs (0.2% accuracy)
-
Frequency Range: 40-70Hz (±0.01Hz resolution)
-
Analog Outputs: 4x 4-20mA (actuator control)
-
-
Communication & I/O
-
Digital I/O:
-
16 programmable inputs (24VDC wetting)
-
10 relay outputs (5A @ 30VDC)
-
-
Communication Ports:
-
Dual RS-485 (Modbus RTU)
-
CANbus J1939
-
Optional Ethernet (IEC 61850)
-
-
-
Power Supply
-
Operating Voltage: 18-32VDC (24V nominal)
-
Power Consumption: 25W max
-
Supercapacitor Backup: 72-hour settings retention
-
Hardware Features
-
Display: 5.7″ TFT LCD (640×480) with capacitive touch
-
Enclosure: IP65-rated aluminum housing
-
Operating Temp: -40°C to +70°C (condensing)
-
Certifications: UL 508, IEC 60255, DNV-GL
Programming & Configuration
-
Configuration Tools:
-
Woodward Toolkit (v6.10+ required for Rev G)
-
Web interface (via Ethernet option)
-
-
Key Parameters:
-
Load ramp rates (1-600 sec adjustable)
-
20+ custom alarm setpoints
-
Black start sequencing
-
Application Profiles
-
Data Centers: Closed transition transfer
-
Marine: MIL-STD-1399 power quality
-
Oil/Gas: SIL2-certified critical loads
-
Microgrids: Renewable integration
Installation Guide
-
CT/PT Wiring:
-
1A CTs: ≤5VA burden
-
120:1 PTs: Class 0.5 accuracy
-
-
Synchroscope Interface:
-
Slip frequency <0.1Hz for close command
-
-
Grounding:
-
<1Ω chassis ground mandatory
-