Condition:Used
Key Specifications
-
Model Identification
-
Part Number: 8440-1801
-
Revision: C (hardware/software version)
-
Series: EasyGen-350 (50B/X variant)
-
Type: Digital genset controller with paralleling capability
-
-
Core Functions
-
Engine Control:
-
Speed governing (isochronous/droop)
-
Automatic start/stop sequencing
-
Protective shutdowns (overspeed, low oil pressure, etc.)
-
-
Generator Monitoring:
-
3-phase voltage/frequency/power measurement
-
Synchronization (auto-sync to bus)
-
-
Load Management:
-
kW/kVAR load sharing (up to 32 units in parallel)
-
Peak shaving capability
-
-
-
Technical Parameters
-
Voltage Inputs:
-
Generator: 0-600V AC L-L (via PTs)
-
Bus: 0-600V AC L-L (for sync)
-
-
Current Inputs: 5A AC (via CTs)
-
Frequency Range: 40-70Hz
-
Analog Outputs: 2x 4-20mA (for actuator control)
-
-
Communication & I/O
-
Digital I/O:
-
8 programmable inputs (24VDC)
-
6 relay outputs (5A @ 30VDC)
-
-
Communication Ports:
-
RS-485 (Modbus RTU)
-
CANbus (J1939)
-
Optional Ethernet (TCP/IP)
-
-
-
Power Supply
-
Operating Voltage: 18-32VDC (24V typical)
-
Power Consumption: 15W max
-
Battery Backup: Supercapacitor for memory retention
-
Hardware Features
-
Display: Backlit LCD (128×64 pixels) with 6-button keypad
-
Enclosure: Aluminum (IP40) or optional ruggedized housing (IP65)
-
Operating Temp: -40°C to +70°C (-40°F to +158°F)
-
Certifications: UL 508, CE, DNV-GL
Programming & Configuration
-
Configuration Tools:
-
PC Software: Woodward Toolkit
-
On-Device: Menu-driven interface
-
-
Programmable Parameters:
-
Start/stop sequences (up to 10 steps)
-
Voltage/frequency setpoints
-
Load transfer thresholds
-
-
Protection Settings:
-
Adjustable trip delays for all protections
-
10+ programmable alarms
-
Typical Applications
-
Standby Generators: Hospitals, data centers
-
Prime Power: Mining, oil/gas
-
Microgrids: Renewable integration
-
Marine: Shipboard power