CONDITION : USED BUT TESTED AND WORKING FINE
Key Features & Specifications
-
Model & Revision
-
Part Number: MRU4A0AB
-
Revision: Y (latest hardware/software updates)
-
Series: High ProTec (Woodward’s protection relay line)
-
-
Primary Protection Functions
-
Over/Under Voltage (59/27):
-
Adjustable thresholds (e.g., 110%–130% for overvoltage, 70%–90% for undervoltage).
-
-
Over/Under Frequency (81O/81U):
-
Typical range: 40–70 Hz (configurable).
-
-
Phase Imbalance (47):
-
Detects voltage unbalance (>5% adjustable).
-
-
Neutral Displacement (59N):
-
For ground fault detection in ungrounded systems.
-
-
-
Inputs & Outputs
-
Voltage Inputs:
-
3-phase + neutral (57–300V AC line-to-line, via PTs).
-
-
Binary Inputs: 4–8 configurable status inputs (e.g., breaker position).
-
Relay Outputs: 6–10 changeover contacts (trip, alarm, load shedding).
-
Communication:
-
RS-485 (Modbus RTU) or optional Ethernet (IEC 61850).
-
-
-
Settings & Programmability
-
Flexible Logic: User-defined trip/alarm conditions via Woodward’s ProTec Plus software.
-
LED Indicators: Real-time status (faults, active protections).
-
Event Logging: Stores 100+ fault records with timestamps.
-
-
Environmental & Certifications
-
Operating Temp: -40°C to +70°C (-40°F to +158°F).
-
Standards: IEEE C37.90 (EMC), IEC 60255 (protection relays).
-
Typical Applications
-
Power Generation: Generator protection (overvoltage due to AVR failure).
-
Industrial Plants: Motor/pump protection from voltage sags/swells.
-
Renewables: Grid-tied solar/wind farm voltage stability.
Wiring & Installation
-
Voltage Inputs:
-
Connect to potential transformers (PTs) for high-voltage scaling.
-
-
Trip Outputs:
-
Wire to circuit breaker coils or alarm panels.
-
-
Communication:
-
RS-485 for SCADA integration (Modbus address must match).
-
Configuration Steps
-
Set Thresholds:
-
Overvoltage: 110% of nominal (e.g., 121V for 110V system).
-
Undervoltage: 85% of nominal (e.g., 93.5V for 110V system).
-
-
Time Delays:
-
Adjust trip delays (0.1–300 sec) to avoid nuisance tripping.
-
-
Test Mode:
-
Simulate faults using secondary injection (verify relay response).
-