Condition:New – Open box
Core Specifications
-
Model: PM5560 (PowerLogic Series 5000)
-
Input Voltage: 50-480V AC L-N (100-830V AC L-L)
-
Current Inputs: 1A or 5A CTs (configurable)
-
Basic Accuracy: 0.2% of reading (voltage/current)
-
Power Accuracy: 0.5% of reading
-
Energy Accuracy: Class 0.5S (IEC 62053-22)
Measurement Capabilities
-
Electrical Parameters:
-
V, A, kW, kVAR, kVA, PF, Hz
-
THDv/THDi up to 63rd harmonic
-
Unbalance (voltage/current)
-
-
Power Quality:
-
Voltage dips/swells
-
Transients recording
-
IEC 61000-4-30 Class A compliance
-
Communication Interfaces
-
Standard Ports:
-
2x Ethernet (Modbus TCP, IEC 61850, DNP3)
-
RS-485 (Modbus RTU)
-
-
Optional:
-
PROFIBUS DP
-
LonWorks
-
BACnet/IP
-
Input/Output Configuration
-
Digital Inputs: 4x (dry contact or 24VDC)
-
Relay Outputs: 2x (5A @ 250VAC)
-
Analog Outputs: 2x 0-20mA / 4-20mA
Display & Interface
-
Front Panel:
-
5.7″ color LCD (320×240)
-
6-button navigation
-
-
Visual Indicators:
-
Multi-color LED status
-
Real-time waveform display
-
Memory & Logging
-
Internal Storage:
-
128MB flash memory
-
30-day data logging (1-min intervals)
-
-
Supported Logs:
-
Min/Max/Avg (configurable periods)
-
Power quality events
-
Load profile data
-
Power Supply
-
Operating Voltage: 85-265V AC/DC
-
Power Consumption: ≤5VA
-
Backup: Supercapacitor (72hr clock backup)
Environmental Ratings
-
Operating Temp: -25°C to +70°C
-
Storage Temp: -40°C to +85°C
-
Humidity: 95% non-condensing
-
Protection: IP40 (front), IP20 (terminals)
Certifications & Compliance
-
Safety: UL 61010-1, IEC 61010-1
-
EMC: EN 61326-1
-
Standards:
-
IEC 62053 (energy metering)
-
IEEE 519 (harmonics)
-
ANSI C12.20 (0.5% accuracy)
-
Typical Applications
-
Critical power monitoring (hospitals, data centers)
-
Energy management systems
-
Power quality analysis
-
Submetering for LEED certification
Reviews